| General information |
| Product type designation | AQ 8xU/I HS |
| HW functional status | From FS01 |
| Firmware version | V2.1.0 |
| • FW update possible | Yes |
| Product function |
| • I&M data | Yes; I&M0 to I&M3 |
| • Isochronous mode | Yes |
| • Prioritized startup | No |
| • Output range scalable | No |
| Engineering with |
| • STEP 7 TIA Portal configurable/integrated from version | V14 / - |
| • STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| • PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| • PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode |
| • Oversampling | Yes |
| • MSO | Yes |
| CiR - Configuration in RUN |
| Reparameterization possible in RUN | Yes |
| Calibration possible in RUN | Yes |
| Supply voltage |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current |
| Current consumption, max. | 320 mA; with 19.2 V supply |
| Power |
| Power available from the backplane bus | 1.15 W |
| Power loss |
| Power loss, typ. | 7 W |
| Analog outputs |
| Number of analog outputs | 8 |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 45 mA |
| Current output, no-load voltage, max. | 20 V |
| Cycle time (all channels), min. | 125 卩s; independent of number of activated channels |