| Degree of efficiency | > 97% @ 24 V Input voltage |
| Derating | > 60°C / 75% load @ 70°C |
| Housing version | Metal, corrosion resistant |
| Humidity | 5-95% relative humidity, Tu = 40°C, without condensation |
| MTBF | | According to Standard | SN 29500 | | Operating time (hours), min. | 44,022 kh | | Ambient temperature | 25 °C | | Input voltage | 24 V | | Output power | 240 W | | Duty cycle | 100 % | | According to Standard | SN 29500 | | Operating time (hours), min. | 3,854 kh | | Ambient temperature | 40 °C | | Input voltage | 24 V | | Output power | 240 W | | Duty cycle | 100 % | | |
| Mounting position, installation notice | Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between. |
| Operating temperature | -40 °C...70 °C |
| Protection degree | IP20 |
| Short-circuit protection | No |
| Surge voltage category | III |